Retrotec DM-2A Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Calculateurs Retrotec DM-2A. DM-2 digital gauge Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 109
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs

Résumé du contenu

Page 2 - What you will learn

 Use a wind dampening kit

Page 3 - What is Pressure?

Imbalanced test fan flow – Solution : common set point 1. What is the total leakage area (EqLA)? (Pick the closest answer) 10 in2 __ , 20 in2 _

Page 4

Uneven building test pressures between floors caused by common set point Click to play video Developed by Retrotec Inc. Exercise 3

Page 5 - There are two

Uneven building test pressures between floors caused by common set point Developed by Retrotec Inc. Exercise 3 Only 1 gauge controls the speed o

Page 6

Uneven building test pressures between floors caused by common set point 1. What is the pressure of the right Simulator Tent? (Pick the closest answ

Page 7 - Bias due to wind and stack

Uneven building test pressures between floors – Solution: individual set points Click to play video Developed by Retrotec Inc. Exercise 4

Page 8 - ◦ Stabilizes readings

Uneven building test pressures between floors – Solution: individual set points Developed by Retrotec Inc. Exercise 4

Page 9 - Testing in windy weather

Uneven building test pressures between floors – Solution: individual set points 1. What is the flow through the left Simulator Tent? (Pick the cl

Page 10 - Use a wind dampening kit

Uneven building test pressures between floors – Solution: individual set point with manual control Click to play video Developed by Retrotec In

Page 11 - What does taking a baseline

Uneven building test pressures between floors – Solution: individual set point with manual control Developed by Retrotec Inc. Exercise 5

Page 12 - 3.Wait until

Uneven building test pressures between floors –Solution: individual set point with manual control 1. What is the flow through the left Simulator Te

Page 13 - The measured baseline

Take a baseline to negate the effects of bias pressure and wind fluctuations.  What does taking a baseline do?

Page 14

1. Press [Baseline] once. 2. Press [Start] once 3.Wait until number is steady then press [ENTER] once to save. The measure baseline is automatically

Page 15

1. Press [Baseline] once 2. Press [Enter] after about 60 seconds. The measured baseline is subtracted from the pressure reading on Channel PrA.

Page 16 - Avoid Problems

Learn when and how the baseline is cleared from each gauge. Leaving the baseline on, or forgetting that it’s off can cause errors during testing.  C

Page 17 - Gauge field check

Residential Pressure Measurement Pressure gauge Troubleshooting

Page 18

Avoid Problems

Page 19 - Cross Port Check

 Insert a T in the tube and connect it to one reference port. Connect the other reference port as shown.  Increase the fan speed and compare Channel

Page 20 - To outside

Learn to perform a calibration check on a digital gauge. It’s a quick and simple way to verify that the gauge is working correctly.

Page 21

Cross Port Check 1 2 3 35.2 Pa 35.6 Pa -35.2 Pa -35.6 Pa 35.2 Pa 35.6 Pa

Page 22 - (2X) the time

 What is pressure?  The importance of pressure in houses  Get to know your pressure gauge  Using a digital pressure gauge  Pressure gauge tests o

Page 23 - Pinched tubes

 A moving tube can generate pressure in the tube. ◦ Do not allow tubes to hang in the path of moving air. Move tubes around and notice the effect 8.0

Page 25 - What can cause problems

Always wait twice (2X) the time averaging period before taking a reading. Time averaging can lead to false results if the time averaging period is not

Page 26 - Range, or

 Pinching or squishing a tube causes the measured pressure to increase Pinched tubes

Page 27 - Some common problems are

 Water trapped in tube compresses air in the tube, even with auto-zero turned ‘ON’.  Shake out the water to clear the pressure.  A single water dr

Page 28 - Introduction

 What can cause problems with measurements?

Page 29

 Selecting the wrong Flow Range, or wrong device can lead to incorrect results. ◦ What happens?

Page 30 - Flex duct

 Some common problems are frequently seen when taking multi-point tests.

Page 31 - 12’ Flex-duct

Introduction Residential Duct Leakage Measurement rev-2011-02-21

Page 32 -  Sample roll of 8” DuctMask

Image Courtesy of The Energy Conservatory Image Courtesy of Retrotec Inc

Page 33

Residential Pressure Measurement What is Pressure?

Page 34 - Pressurization test

Calibrated Fan Flex duct Flex duct flange Flex duct Image Courtesy of Retrotec Inc Image Courtesy of The Energy Conservatory

Page 35 - Prepare ducts and house

A DucTester system includes:  DU-220 Fan with 3 flow rings + case  12’ Flex-duct  DM-2A Digital Manometer + bag  Static pressure probe  20’ umbil

Page 36 - Duct testing guides

Duct Blaster includes:  Duct Blaster fan with 3 flow rings + case  DG-700 Digital Pressure and Flow Gauge  12’ flex duct  Duct Blaster Training vi

Page 37 - Step 1: Connect to ducts

Open Ring 1 (A1) Ring 2 (B2) Ring 3 (C3 on gauge) 600-1000 cfm 225-800 cfm 90-300 cfm 10-125 cfm Low Mid Open 5-25 cfm 25-125 cfm 100-600 cfm Minn

Page 38

5 step, Total duct Pressurization test Residential Duct Leakage Measurement

Page 39

1. Connect to ducts 2. Prepare ducts and house 3. Connect gauge & fan (pressurization) 4. Measuring 5. No results displayed 5 step, Total duct Pre

Page 40

Duct testing guides

Page 41

Step 1: Connect to ducts Image Courtesy of Retrotec Inc Image Courtesy of Retrotec Inc Image Courtesy of The Energy Conservatory Image Courtesy of The

Page 43

Images Courtesy of The Energy Conservatory

Page 44

What is Pressure?

Page 45

Step 2: Prepare ducts and house Image Courtesy of Retrotec Inc

Page 49

25 Pa 90 cfm

Page 50 - Turn the gauge On

Image Courtesy of Retrotec Inc

Page 52

Fan Pressure Tap Electrical Connection Image Courtesy of The Energy Conservatory

Page 55

There are two types of pressure that can be measure on a digital gauge.

Page 56 - Troubleshooting

Turn the gauge On Press: x3 x3 x2 ON/ OFF Press: Press: x2 After being set up once, the gauge will return to the previous settings.

Page 57 -  Both channels

Manually adjust fan speed Image Courtesy of Retrotec Inc Image Courtesy of The Energy Conservatory

Page 58

Open Mid

Page 60

Open Ring 1 (A1) Ring 2 (B2) Ring 3 (C3) 600-1000 CFM 225-800 CFM 90-300 CFM 10-125 CFM Open Mid Low 100-600 CFM 25-125 CFM 5-25 CFM Minneapolis Duct

Page 61

Image courtesy of Retrotec Inc Image courtesy of The Energy Conservatory Image Courtesy of Retrotec Inc -25 Pa 90 cfm

Page 62 -  Duct leakage to outdoors

• Not able to reach target pressure • Check covers on all registers • Tape may be being blown off during pressurization • Duct system just too leaky t

Page 63 - Pressurization to outdoors

 Connect the red and yellow ports.  Both channels should have same reading within 1%.

Page 64 -  The leaks measured

Image Courtesy of Retrotec Inc

Page 65 - 100 cfm

Pressurization leakage to outdoors Residential Duct Leakage Measurement

Page 66 - Leak location

 Stack effects & Wind effects Measure indoor/outdoor bias pressures caused by: -1.0Pa To outside

Page 67 - Duct Simulator setup

Image Courtesy of Retrotec Inc

Page 69 - Guiness World Record

After completing the total duct leakage test, a duct leakage to the outdoors test can be completed by adding a door fan to the test setup.  Duct leak

Page 70

Pressurization to outdoors Image Courtesy of Retrotec Inc 25 Pa 25 Pa 25 Pa 0 Pa 40 cfm 40 cfm

Page 71

 Duct leakage to outdoors test  The duct leakage to the outdoors test neutralizes air leakage between the duct and interior of the house, by maintai

Page 72

Pressurization to outdoors – Single gauge 25Pa 100 cfm Image Courtesy of Retrotec Inc 25 Pa 40 cfm 25 Pa 40 cfm

Page 73 - Acceptable air leakage?

Leak location Residential Duct Leakage Measurement

Page 74 - Real life test: EMAD

Duct Simulator setup  Setup the duct simulator with leakage to the house and to the outdoors (with the house simulator tent).  Build your own simula

Page 75 - Real life test: BTC

Large Building Testing Developed by Retrotec Inc.

Page 76 - Real life test: Retrotec

Guiness World Record 15,000,000 cubic feet

Page 77 - Face page and graphs for MFT

Bias due to wind and stack Bias pressures under windy conditions

Page 79

Year of Construction Year of Air-barrier retrofit? Number of Stories Floor Area Enclosure Area Tested Permeablity ft2 ft2 cfm/ft2 @75Pa 2011 -

Page 80

Year of Construction Year of Air-barrier retrofit? Number of Stories Floor Area Enclosure Area Tested Permeablity ft2 ft2 cfm/ft2 @75Pa 2012 -

Page 81

Acceptable air leakage? For a 4 story building, 120 x 110 x 8 ft, n=0.65 CFM75/ ft2 USA ASHRAE 90.1 Leaky 0.60 USA Washington State 0

Page 82 - Test Scenarios

Real life test: EMAD Antwerp, Belgium • Envelope Area = 11,250 m2 • 0.601 CFM/ft2 @ 75Pa • 8.22 m3/h/m2

Page 83 - FanTestic software

Real life test: BTC South Carolina, USA • Envelope A = 136,820ft2 • 0.08 CFM/ft2 @ 75Pa • 1.5 m3/h/m2

Page 84 - Problem 1

Real life test: Retrotec Vancouver, Canada • Envelope Area = 25,000 ft2 • 0.4 CFM/ft2 @ 75Pa • 7.3 m3/h/m2

Page 85 - Solution

Face page and graphs for MFT

Page 87

Estimating how many fans you need

Page 88 - Problem 3A

 Press [Time Avg], until test pressure varies less than 1Pa.  Wait for 2X time average period before taking a reading. ◦ Stabilizes readings

Page 89 - Problem 3B

Calculation based on a desired leakage requirement

Page 90

Calculation using Retrotec’s ‘Number of Fan Calculator’ Spreadsheet

Page 91 - Connections that work best

Test Scenarios (“Individual Control” with FanTestic) Developed by Retrotec Inc.

Page 92

FanTestic software

Page 93

One Zone: Testing a single-zone enclosure requiring multiple fans. Problem 1

Page 94 - Exercises

One Zone: Testing a single-zone enclosure requiring multiple fans. Solution

Page 95

Multiple Zones: Testing multiple zones requiring one fan on each separate zone. (These zones can be adjacent rooms or separated floors) Problem 2

Page 96 - Red tubes attached

Solution Multiple Zones: Testing multiple zones requiring one fan on each separate zone. (These zones can be adjacent rooms or separated floors)

Page 97

Multiple Zones: Testing multiple zones requiring multiple fans on each separate zone. (These zones can be adjacent rooms or separated floors) Problem

Page 98

Multiple Zones: Testing multiple zones requiring multiple fans on each separate zone. (These zones can be adjacent rooms or separated floors) Problem

Page 99

 Use [@ Pressure] key (if available)  Increase Time Average to minimize fluctuation ◦ Wait at least double the time averaging period before taking a

Page 100 - Imbalanced test fan flow –

Multiple Zones: Testing multiple zones requiring multiple fans on each separate zone. (These zones can be adjacent rooms or separated floors) Solution

Page 101 - Developed by Retrotec Inc

Connections that work best (Control cables) Developed by Retrotec Inc.

Page 104

Large Building Testing Exercises Developed by Retrotec Inc.

Page 105

Imbalanced test fan flow caused by individual set points Click to play video Developed by Retrotec Inc. Exercise 1

Page 106

Control Cable Control Cable Imbalanced test fan flow caused by individual set points Exercise 1 Red tubes attached with T-connecters

Page 107

Imbalanced test fan flow caused by individual set points 1. What is the difference between the two Door Fan speeds? (Pick the closest answer) 2%

Page 108

Imbalanced test fan flow – Solution : common set point Click to play video Developed by Retrotec Inc. Exercise 2

Page 109

Control Cable Imbalanced test fan flow caused by individual set points Exercise 2 Only 1 gauge controls the speed of both fans

Commentaires sur ces manuels

Pas de commentaire