7. Set up the gauge to display Duct Leakage Results
Read the Total Duct Leakage results directly from the gauge. Change units by tapping on Channel B. In
order to compare duct systems in different homes/buildings, it is necessary to normalize the leakage
results for the size of the HVAC system and the size of the building. The two most common variables
used to normalize duct leakage are total HVAC flow rate and the floor area of the building.
Figure 24: Some of the most common results that can be read directly off the gauge.
7.1 Mode setup for duct testing in the US
The Table below shows what settings will directly calculate the results required for testing compliance
with the codes adopted in the various states.
Table 3: Gauge Mode Setup for US state Codes and programs for Duct Testing
Northwest
ENERGY STAR
Homes
VT GA CT DE
GA ID IL IO
MA NC NH NJ
NY OH TX
MD
Flow per Area of
Conditioned floor area
(Flow per Area) @
Pressure
Grey areas in the table indicate those results are not needed for those programs but can be turned on or
off any time they may be needed. The “@ Pressure” value for Flow measurement is set at the value
required for duct testing.